TECHNICAL DESCRIPTION | |
1. Power supply is provided from transformer substation (400kVA), | 380V, 50Hz |
Max. capacity of tested transformer, kVA | 4000 |
Max. voltage of tested transformer, kV | 10 |
Max. consumed capacity, kVA | ne bolee 50 |
Station overall dimensions after installation should not exceed, mm | 6000x9000x3000 |
Total station mass should be not more than, kg | 4000 |
Running time of overall testing schedule, min | not more than 50 |
Duration of continuous running, hour | not less than 8 |
METROLOGICHESKIE HARAKTERISTIKI SREDSTV IZMERENIY STANTSII (PREDEL POGRESHNOSTI): | |
AC current, A | 0..150 (0,3 %) |
AC voltage, V | 0..800 (0,3 %) |
Capacity, kVA | 10…107 (3 %) |
Insulating resistance, Ω | 0,0001…50 (0,5 %) |
Active winding resistance, transformation ratio, Om | 0,8-100 (0,4%) |
Fig1. Equipment lay out |